Case of the Monstrous Moisture – Mystery of Moisture (Damp / Seepage) Laden Building

How Thermal Imaging Technology, Latest Tools and a trained Home Inspection Team helped in assessing and finding source & solution to serious non-identifiable damp / seepage problem in a reputed Club of Bengal.

Moisture Laden Heritage Building (Façade + Ground + 3 Floors + Roof)

Planning for Home Renovation

It made sense to do a thorough Damp / Seepage Inspection through Thermal Imaging – Infrared Technology

Roofs, parapets and other exposed parts of a building are most susceptible to rain penetration, especially where access for maintenance is difficult. Junctions in roofs are potential trouble. Hairline cracks in pointing and render invariably admit moisture.

 
StepArea of WorkFunctionPurposeRepair / Renovation Work
1Water tanks and tap at the roofPlumbingTo Stop Constant flow of water noted under the water tanks and near drainage pipesInstall automatic over flow sensors at water tanks (to be done by professional vendor). The dripping tap to be repaired.
2Drain Pipe & Slab at the RoofPlumbingTo stop the water from entering into the parapet wall at the rain water drainageShort piece of PVC pipe to be fixed inside gutter, so that flow of water would be: Roof > PVC pipe > vertical CI pipe.
3Entire roof drainage linesPlumbingTo stop the water from entering into the parapet wall at the rain water drainageBroken CI over flow line to be replaced and connected directly to the vertical CI pipe.
4Below LMR roomPlumbingTo check water stagnation at LMRFrom the slab below LMR, all materials to be removed, slab to be cleaned and repaired for proper drainage.
5Parapet wallCivilTo check the damage due to growth of green plants, moss and algae at the structureAll growth at the parapet wall to be completely removed and treated with light acid.
6Wherever applicableCivilTo stop soaking of water and developing pockets of water at the bare and hollow brick workHollow brickwork to be completely re-plastered with Cement – sand (1:4) mortar with Latex additive and given neat cement finishing. Or It should be filled with brick concrete and re-plastered as above.
7RoofCivilTo stop rain water infiltration from cracks at the roof and parapet wall and the ones developed on removing the plantsSurface preparation / Cleaning – All loose material, dust, debris, oil paint, grease etc. to be completely removed with wire brush.
Pre wet the surface with water and allow it dry slightly. As applicable, Cement – sand (1:4) mortar with Latex additive or masonry silicone sealant to be filled and compacted into the cracks. No moisture should be in the crack during filling.
8Slab and roof junctionCivilTo make a seamless junction, as Huller at the slab and roof junction is not adequate,After surface hacking and thorough cleaning with wire brush, 3 inch X 3 inch wall and roof junction fillet to be made on the entire Roof and wall junction.
9After completion of the aforesaid, affected areas to be treated as follows:

 

  • Affected area paint & putty to be completely scraped of till cement plaster layer.
  • Natural air ventilation to be given in the affected area for minimum 15 days before further finishing.
  • Finishing (including water based paint finishing to be given as per paint manufacturer specification.
  • FYI: The walls to be given ventilation on regular basis.

Conclusion: Identifying the source of moisture is the most important step in these cases and also a very critical one. These inspections involve qualified experienced experts. MACJ – A Buyers Choice Home Inspections is glad to be bestowed with such team who can correctly and precisely identify the issue/s with a simple solution/s. We should also applaud the client who proved wise enough to engage MACJ – A Buyers Choice Home Inspections to solve the problem. Not only did the MACJ team solve it successfully but also saved the client from major future damages which would have also resulted in incurring a lot of money. Our recommendations were also pocket friendly.

Renovation Parameters Before MACJ InspectionRenovation after inspection By MACJ – A Buyer’s Choice
Short term solution as source not identifiableLong term solution as the source of seepage identified
Damage to the StructureMostly Non-destructive solution
High Cost of Repair / Renovation – Rs. 12 – 15 lacsLow Cost of Repair / Renovation – Rs. 4 – 5 lacs

Case Study Summary

Classic case of mystery water seepage from a false ceiling having a non-identifiable source

Classic case of mystery water seepage from a false ceiling having a non-identifiable source Waterproofing / Other Vendors’ SolutionBefore MACJ […]

Case of the Monstrous Moisture – Mystery of Moisture (Damp / Seepage) Laden Building

Case of the Monstrous Moisture – Mystery of Moisture (Damp / Seepage) Laden Building How Thermal Imaging Technology, Latest Tools […]

Case of persisting damp / seepage issues even after Refurbishing and Rectification work in a Duplex Home

Case of persisting damp / seepage issues even after Refurbishing and Rectification work in a Duplex Home The Background A […]

Scroll to Top